Inverter Size Calculator
Add AC devices that may run together to estimate continuous inverter output and startup demand.
Your inputs
AC device
Total while starting; repeat running W if there is no surge.
Inverter size estimate
Estimated inverter output
Continuous AC output needed while the selected devices run together.
—
Same W scale. Startup values are separate scenarios; compare their duration with the inverter manual.
Startup scenarios explained
Startup scenarios
Peak if one device starts at a time
—
Peak if all devices start together
—
Enter the AC devices you expect to run at the same time.
Compare both watts and surge duration with the inverter manual. Battery, BMS and wiring capability are separate checks.
Edit your inputsHow this calculator works
Formula, worked example, assumptions and sources
Continuous W = sum of quantity × running W for devices operating together. Startup W is the total AC power a device draws while starting. For one device starting while all other devices are already running, add the largest startup W − running W of a single device to continuous W. If all devices start together, add quantity × startup W across all rows.
For example, take three illustrative devices, one of each: A uses 600 W running and 1,200 W starting; B uses 300 W running and 900 W starting; C uses 100 W both running and starting. These are arithmetic examples, not ratings or presets for real appliances.
- Running together: 1,000 W = 600 + 300 + 100.
- One unit starting: 1,600 W = 1,000 + 600, using the largest single increase above running power.
- All starting together: 2,200 W = 1,200 + 900 + 100.
The lower startup figure applies when one device starts while the others are already running. If both startup loads can overlap, that assumption no longer describes the event. Compare the applicable demand and its duration with the inverter’s ratings.
Use real AC input watts, not DC battery draw, Wh/day, cooking output, or volts × amps without power factor. A device's starting peak may be specified as current or VA rather than W; do not treat those units as interchangeable. No generic surge multiplier or safety margin is added. Actual peak duration and the inverter's rated duration must be compared separately.
These are AC output estimates, not a recommendation for a specific inverter. Compare the results with the inverter's watt and VA ratings, surge duration, output voltage and waveform, and any temperature derating. The battery and wiring must also be able to supply the required DC input; this calculator does not check them.
References: Victron Inverter VE.Direct 120V manual lists continuous W, time-limited output and peak W with durations; Victron inverter selection guidance notes simultaneous loads and battery support. See the site methodology.