Can I Run This on My Generator?

Check your simultaneous AC loads against your generator’s running and starting watt ratings.

Your generator ratings

Continuous output for your fuel and operating conditions.

Starting watts for the same fuel and conditions; check duration.

Where do I find these ratings?

Use the generator’s continuous AC output rating in watts for the fuel type and operating conditions you expect. Do not use its starting or maximum rating.

Use the starting watt rating for the same generator, fuel type, and operating conditions. Check how long the generator can sustain this output.

Devices you want to run
Where do I find running and startup watts?
Check the device label or manual for electrical input power and starting demand, or use a suitable measurement. Startup watts are the total power while starting, not extra watts; use running watts again if there is no surge. Include only devices that may run together on this source. For a charger, use its AC input, not DC output. Watts, VA and amps are different values; VA or amps alone do not give real watts without the relevant voltage and power factor. If startup watts are unknown, confirm them before relying on the comparison. No startup multiplier is assumed.

AC device 1

Total while starting; repeat running W if there is no surge.

View result

Generator comparison

Your generator load check

Compared with the generator watt ratings you entered.

—

Demand against generator ratings
While running —
One device starts —
All devices start —

Bars show demand; vertical marks show entered ratings on the same W scale. Red means over the W rating, not a safety assessment.

Watt ratings alone do not confirm operation or safety. Check startup duration, circuit limits and operating conditions separately.

Edit your inputs

How this calculator works

Formula, worked example, assumptions and sources

The Generator Size Calculator method gives three AC load values: continuous W = sum of quantity × running W; peak with one device starting (W) = continuous W + largest (startup W − running W); and peak with all devices starting together (W) = sum of quantity × startup W. A device’s startup watts are its total power draw while starting, not an extra amount.

Compare continuous load with the generator’s running W rating. Compare each startup scenario with its starting W rating. The displayed difference is entered rating − required W. A positive difference means the load is below the entered watt rating. A negative difference means the load exceeds the rating. Zero means the load is exactly at the limit. For example, a 1,475 W running load, a 2,675 W peak with one device starting, and a 3,175 W peak with all devices starting together compared with 2,000 W running / 3,000 W starting ratings give differences of +525 W, +325 W, and −175 W respectively.

Select the startup scenario that could actually happen. These W ratings alone do not show whether the peak can last long enough or whether voltage, frequency, receptacle current and power factor are compatible. Use actual AC input watts for appliances. Do not treat VA or DC battery draw as the same value. No automatic surge multiplier or safety margin is added.

This comparison does not confirm that your setup will operate safely or correctly. Check startup duration, voltage and frequency, VA/current limits, receptacle and circuit limits, derating, and motor-starting requirements in the generator manual. It does not assess wiring, transfer equipment, fuel use, or exhaust safety.

References: Generac portable generator owner’s manual explains simultaneous running loads and motor startup demand; Champion’s explanation of running and starting W notes that a peak rating lasts only briefly. See the site methodology.

Calculations run in your browser. How your data is used